- Automatic night reduction (can be activated)
- Thermal insulation shells
- Fitted with a thermal insulation shell
Installation Length 130/170/180 mm
Permissible operating pressure 10 bar
Permissible operating temp. +15°C to +110°C
Required operating pressure at: 500 m a.s.l.
at 75°C water temperature 0.05 bar
at 90°C water temperature 0.30 bar
at 110°C water temperature 1.10 bar
For every ±100 m altitude ±0.01 bar
Weight 2.3 kg
Voltage 1 x 230 V, 50 Hz
Current
Regulation 0.05...0.19 A
min 0.05A
Power
Regulation 5...22 W
min 5 W
To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.
Installation Length 130/170/180 mm
Permissible operating pressure 10 bar
Permissible operating temp. +15°C to +110°C
Required operating pressure at: 500 m a.s.l.
at 75°C water temperature 0.05 bar
at 90°C water temperature 0.30 bar
at 110°C water temperature 1.10 bar
For every ±100 m altitude ±0.01 bar
Weight 2.3 kg
Voltage 1 x 230 V, 50 Hz
Current
Regulation 0.05...0.38 A
min 0.05A
Power
Regulation 5...45 W
min 5 W
To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.
Ambient temperature Media Temperature
oC min.oC max.oC
15 15 110
30 30 110
35 35 90
40 40 70
The pump is fitted with internal electric motor protection and requires no external motor protection.
The pumps AX 12,-1,-2 are fitted with a thermal insulation shell.
Ambient temperature Media Temperature
oC min.oC max.oC
15 15 110
30 30 110
35 35 90
40 40 70
The pump is fitted with internal electric motor protection and requires no external motor protection.
The pumps AX 13,-1,-2 are fitted with a thermal insulation shell.