- Power limiting (can be deactivated)
- Fault or operating message (switchable)
Installation Length
A 402 V2 220 mm
A 402-1 V2 250 mm
Permissible operating pressure 6–16 bar
Permissible operating temp. +15°C to +95°C
Ambient temperature max. 40°C
Required operating pressure at: 500 m a.s.l.
at 75°C water temperature 0.40 bar
at 95°C water temperature 0.85 bar
For every ±100 m altitude ±0.01 bar
Weight 14.5 kg
Voltage 1 x 230 V, 50 Hz
Current
Regulation 0.25...2 A
min 0.33 A
Power
Regulation 25...420 W
min 30...65 W
To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.
Ambient temperature Media Temperature
oC min.oC max.oC
15 15 95/110*
30 30 95/110*
35 35 90/110*
40 40 70/110*
The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).
Optional:
Installation Length 270 mm
Permissible operating pressure 6–16 bar
Permissible operating temp. +15°C to +95°C
Ambient temperature max. 40°C
Required operating pressure at: 500 m a.s.l.
at 75°C water temperature 0.20 bar
at 95°C water temperature 0.65 bar
For every ±100 m altitude ±0.01 bar
Weight 18.5 kg
Voltage 1 x 230 V, 50 Hz
Current
Regulation 0.25...1.3 A
min 0.4 A
Power
Regulation 35...275 W
min 3...65 W
To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.
Ambient temperature Media Temperature
oC min.oC max.oC
15 15 95/110*
30 30 95/110*
35 35 90/110*
40 40 70/110*
The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).
Optional:
Installation Length 270mm
Permissible operating pressure 6–16 bar
Permissible operating temp. +15°C to +95°C
Ambient temperature max. 40°C
Required operating pressure at: 500 m a.s.l.
at 75°C water temperature 0.10 bar
at 95°C water temperature 0.65 bar
For every ±100 m altitude ±0.01 bar
Weight 19 kg
Voltage 1 x 230 V, 50 Hz
Current
Regulation 0.45...3.4 A
min 1 A
Power
Regulation 70...720 W
min 70...200 W
To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.
Ambient temperature Media Temperature
oC min.oC max.oC
15 15 95/110*
30 30 95/110*
35 35 90/110*
40 40 70/110*
The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).
Optional:
Installation Length 340 mm
Permissible operating pressure 6–16 bar
Permissible operating temp. +15°C to +95°C
Ambient temperature max. 40°C
Required operating pressure at: 500 m a.s.l.
at 75°C water temperature 0.35 bar
at 95°C water temperature 1.45 bar
For every ±100 m altitude ±0.01 bar
Weight 22 kg
Voltage 1 x 230 V, 50 Hz
Current
Regulation 1.2...2.4 A
min 0.7 A
Power
Regulation 50...515 W
min 50...145 W
To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.
Ambient temperature Media Temperature
oC min.oC max.oC
15 15 95/110*
30 30 95/110*
35 35 90/110*
40 40 70/110*
The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).
Optional:
Installation Length 340 mm
Permissible operating pressure 6–16 bar
Permissible operating temp. +15°C to +95°C
Ambient temperature max. 40°C
Required operating pressure at: 500 m a.s.l.
at 75°C water temperature 0.35 bar
at 95°C water temperature 1.45 bar
For every ±100 m altitude ±0.01 bar
Weight 23 kg
Voltage 1 x 230 V, 50 Hz
Current
Regulation 0.48...4.3 A
min 1 A
Power
Regulation 70...220 W
min 70...220 W
To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.
Ambient temperature Media Temperature
oC min.oC max.oC
15 15 95/110*
30 30 95/110*
35 35 90/110*
40 40 70/110*
The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).
Optional: