Call Us 22517474 or 25733343
  • Power limiting (can be deactivated)
  • Fault or operating message (switchable)

Options

Signal module

  • Operating message
  • External ON/OFF
  • External minimum speed – Twin pumps function

Control module

  • External speed 0–10V/0–20mA
  • External ON/OFF
  • PWM Multitherm interface
  • Twin pumps function

 

Thermal Insulation Shells

Construction set for offset electronics installation

A 402 V2, A402-1 V2

Installation Length

A 402 V2 220 mm

A 402-1 V2 250 mm

Permissible operating pressure 6–16 bar

Permissible operating temp. +15°C to +95°C

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.40 bar

at 95°C water temperature 0.85 bar

For every ±100 m altitude ±0.01 bar

Weight 14.5 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.25...2 A

min 0.33 A

Power

Regulation 25...420 W

min 30...65 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

15 15 95/110*

30 30 95/110*

35 35 90/110*

40 40 70/110*

The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).

Optional:

  • Thermal insulation shell
  • Control module, signal module
  • * construction set for offset electronics installation

A 501 V2

Installation Length 270 mm



Permissible operating pressure 6–16 bar

Permissible operating temp. +15°C to +95°C

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.20 bar

at 95°C water temperature 0.65 bar

For every ±100 m altitude ±0.01 bar

Weight 18.5 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.25...1.3 A

min 0.4 A

Power

Regulation 35...275 W

min 3...65 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

15 15 95/110*

30 30 95/110*

35 35 90/110*

40 40 70/110*

The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).

Optional:

  • Thermal insulation shell
  • Control module, signal module
  • * construction set for offset electronics installation

A 502 V2

Installation Length 270mm


Permissible operating pressure 6–16 bar

Permissible operating temp. +15°C to +95°C

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.10 bar

at 95°C water temperature 0.65 bar

For every ±100 m altitude ±0.01 bar

Weight 19 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.45...3.4 A

min 1 A

Power

Regulation 70...720 W

min 70...200 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

15 15 95/110*

30 30 95/110*

35 35 90/110*

40 40 70/110*

The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).

Optional:

  • Thermal insulation shell
  • Control module, signal module
  • * construction set for offset electronics installation

A 651 V2

Installation Length 340 mm

Permissible operating pressure 6–16 bar

Permissible operating temp. +15°C to +95°C

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.35 bar

at 95°C water temperature 1.45 bar

For every ±100 m altitude ±0.01 bar

Weight 22 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 1.2...2.4 A

min 0.7 A

Power

Regulation 50...515 W

min 50...145 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

15 15 95/110*

30 30 95/110*

35 35 90/110*

40 40 70/110*

The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).

Optional:

  • Thermal insulation shell
  • Control module, signal module
  • * construction set for offset electronics installation

A 652 V2

Installation Length 340 mm

Permissible operating pressure 6–16 bar

Permissible operating temp. +15°C to +95°C

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.35 bar

at 95°C water temperature 1.45 bar

For every ±100 m altitude ±0.01 bar

Weight 23 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.48...4.3 A

min 1 A

Power

Regulation 70...220 W

min 70...220 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

15 15 95/110*

30 30 95/110*

35 35 90/110*

40 40 70/110*

The pump is fitted with internal electric motor protection and requires no external motor protection. The pump is provided with fault or operating message (switchable).

Optional:

  • Thermal insulation shell
  • Control module, signal module
  • * construction set for offset electronics installation