Call Us 22517474 or 25733343
  • Power limiting (can be deactivated)
  • Fault or operating message (switchable)
  • Construction set for offset electronics installation

Options

Signal module

  • Operating message
  • External ON/OFF
  • External minimum speed
  • Twin pumps function

Control module

  • External speed 0–10V/0–20mA
  • External ON/OFF
  • PWM Multitherm interface
  • Twin pumps function

A 404 V2 KW, A 402-1 V2 KW

Installation Length

A 402 V2 KW 220 mm

A 402-1 V2 KW 250 mm

Permissible operating pressure 6-16 bar

Permissible operating temp. -10°C to +110°C*

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.10 bar

at 95°C water temperature 0.85 bar

For every ±100 m altitude ±0.01 bar

Weight 16.5 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.25...2 A

min 0.33 A

Power

Regulation 25...420 W

min 30...65 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

max. 40 -10 110

The pump is suitable for cold water application.
The pump is fitted with internal electric motor protection and requires no external motor protection.
The pump is provided with fault or operating message (switchable).

Optional:

  • Control module, signal module

A 501 V2 KW

Installation Length 270 mm


Permissible operating pressure 6-16 bar

Permissible operating temp. -10°C to +110°C*

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.10 bar

at 95°C water temperature 0.65 bar

For every ±100 m altitude ±0.01 bar

Weight 20.5 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.25...1.3 A

min 0.4 A

Power

Regulation 35...275 W

min 30...65 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

max. 40 -10 110

The pump is suitable for cold water application.
The pump is fitted with internal electric motor protection and requires no external motor protection.
The pump is provided with fault or operating message (switchable).

Optional:

  • Control module, signal module

A 502 V2 KW

Installation Length 270 mm


Permissible operating pressure 6-16 bar

Permissible operating temp. -10°C to +110°C*

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.20 bar

at 95°C water temperature 0.65 bar

For every ±100 m altitude ±0.01 bar

Weight 21 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.45...3.4 A

min 1 A

Power

Regulation 70...720 W

min 70...200 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

max. 40 -10 110

The pump is suitable for cold water application.
The pump is fitted with internal electric motor protection and requires no external motor protection.
The pump is provided with fault or operating message (switchable).

Optional:

  • Control module, signal module

A 651 V2 KW

Installation Length 340 mm

Permissible operating pressure 6-16 bar

Permissible operating temp. -10°C to +110°C*

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.35 bar

at 95°C water temperature 1.45 bar

For every ±100 m altitude ±0.01 bar

Weight 24 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 1.2...2.4 A

min 0.7 A

Power

Regulation 50...515 W

min 50...145 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

max. 40 -10 110

The pump is suitable for cold water application.
The pump is fitted with internal electric motor protection and requires no external motor protection.
The pump is provided with fault or operating message (switchable).

Optional:

  • Control module, signal module

A 652 V2 KW

Installation Length 340 mm

Permissible operating pressure 6-16 bar

Permissible operating temp. -10°C to +110°C*

Ambient temperature max. 40°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.35 bar

at 95°C water temperature 1.45 bar

For every ±100 m altitude ±0.01 bar

Weight 25 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.48...4.3 A

min 1 A

Power

Regulation 70...930 W

min 70...220 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

max. 40 -10 110

The pump is suitable for cold water application.
The pump is fitted with internal electric motor protection and requires no external motor protection.
The pump is provided with fault or operating message (switchable).

Optional:

  • Control module, signal module