Call Us 22517474 or 25733343
  • Automatic night reduction (can be activated)
  • Thermal insulation shells
  • Fitted with a thermal insulation shell

AX 12, -1, -2, -3, -4

Installation Length 130/170/180 mm

Permissible operating pressure 10 bar

Permissible operating temp. +15°C to +110°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.05 bar

at 90°C water temperature 0.30 bar

at 110°C water temperature 1.10 bar

For every ±100 m altitude ±0.01 bar

Weight 2.3 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.05...0.19 A

min 0.05A

Power

Regulation 5...22 W

min 5 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

AX 12, -1, -2, -3, -4

Installation Length 130/170/180 mm

Permissible operating pressure 10 bar

Permissible operating temp. +15°C to +110°C

Required operating pressure at: 500 m a.s.l.

at 75°C water temperature 0.05 bar

at 90°C water temperature 0.30 bar

at 110°C water temperature 1.10 bar

For every ±100 m altitude ±0.01 bar

Weight 2.3 kg

Voltage 1 x 230 V, 50 Hz

Current

Regulation 0.05...0.38 A

min 0.05A

Power

Regulation 5...45 W

min 5 W

To avoid the formation of condensation the media temperature must always be higher than the ambient temperature.

Ambient temperature Media Temperature

oC min.oC max.oC

15 15 110

30 30 110

35 35 90

40 40 70

The pump is fitted with internal electric motor protection and requires no external motor protection.

The pumps AX 12,-1,-2 are fitted with a thermal insulation shell.

Ambient temperature Media Temperature

oC min.oC max.oC

15 15 110

30 30 110

35 35 90

40 40 70

The pump is fitted with internal electric motor protection and requires no external motor protection.

The pumps AX 13,-1,-2 are fitted with a thermal insulation shell.